The zone expander board can accommodate up to (4) initiating device zones.
Two zone cards per expander board with (2) initiating device zones per card.
Zones can be implemented as Class A/B detection, waterflow or switch
supervisory circuits depending on the card type being utilized. It can also
accommodate (2) alarm notification appliance cards (AE-91) with (1) notifi-
cation appliance circuit per card.
H@1>45B
?1B4
9C@<1I
&1>5<
* For zone field wiring see Expander Board field wiring page of manual. For AE-91 field wiring see Option “U” page of
this manual.
Also reference the Installation Wiring Diagram (IWD)
** For solenoid circuit field wiring see RS-1 field wiring page of this manual,
Also reference the Installation Wiring Diagram (IWD)
&&""%(+"")*)/)*#)%$"/
Standard expander board: Used to increase system capabilities.
Accommodates up to (2) cards
#
Metered expander board: Used to increase system capabilities and
compatible with alarm point location meter. Accommodates up to (2)
cards
0 Standard system zone card: Contains (2) Detection Circuits per card.
0# Metered system zone card: Contains (2) Detection Circuits per card (Metered zone card requires EB-91AM)
0- Waterflow zone card: Contains (2) Detection Circuits per card.
) Switch Supervisory zone card: Contains (2) Detection Circuits per card.
)$" Non-Latching switch supervisory zone card: Contains (2) Detection Circuits per card.
Alarm Notification Appliance circuit card: Contains (1) Alarm Notification Appliance circuit per card.
() Solenoid release circuit card: Contains (1) Solenoid Release Circuit & (1) Detection Circuit per card.