transferred to the release module(s), a voltage output is initiated to
operate the normally de-energized solenoid or relay thus activating
t
he extinguishing agent release sequence.
O
ption H (Two 24 VDC Solenoid Monitor & Release
Circuits)
Option H consists of the standard RM-2 Solenoid Release
module which provides two independent 24 VDC release out-
put circuits. Each release circuit is fused and supervised for open
a
nd shorted conditions and provides a disconnect switch on the
module to deactivate the circuit during system service. Each
circuit is also provided with a red solenoid trip LED to confirm
activation and one set of normally open auxiliary alarm contacts
rated 1 amp @ 24 VDC. This option has been approved for
actuation of FM Solenoid Groups A, B, D, E, F and G.
Option HH (Two 24 VDC Star Model D Deluge Valve
Monitor & Release Circuits)
This option utilizes the RM-2D Release Module which has been
specifically designed for those applications that require operation
of the Star Model D Deluge Valve. The RM-2D Release
Module (Option HH) provides all of the same product features
described for the RM-2 module (Option H). This option is the
only model that is FM Approved for operation of the Star
Model D Deluge Valve, FM Solenoid Group C.
Options J & JJ (Two High Voltage Solenoid Monitor &
Release Circuits)
Utilizing the RM-2 Release Module with power switching
relays, Option J (120 VAC) and Option JJ (250 VDC) provide
supervision and initiating power for high voltage solenoids.
Audible Expander Module Option K
The Audible Expander Module, Model AE-2, provides the
2600HD with two additional supervised alarm signaling circuits
(Notification Appliance Circuits) which may be used for general
alarm signaling or operated selectively by input zone. Each power
limited signaling circuit reverses polarity upon alarm and may be
wired in either a Class A (Styles X & Z) or Class B (Styles W & Y)
configuration. Each AE-2 circuit can be separately configured in
either a latching or non-latching mode, and is rated for a maximum
output of 1.5 amp.
Built-in Alarm Indicating Signaling Device Option L
This option provides a built-in alarm signaling device which
activates upon any common alarm condition. This audible device
produces a short intermittent pulsed signal which differentiates the
alarm warning sound from the systems common trouble signal.
This device is not intended for evacuation or life safety audible
alarm signaling.
Auxiliary Relays Options M, N, P, Q, R & S
The 2600HD Series offers a wide range of system relay options
designed to meet the most demanding functional operating require-
ments. Features such as plug-in sockets for easy replacement, timing
functions, heavy duty contacts and customer specified operating
logic all serve to make the 2600HD System the first choice for
demanding industrial applications.
Option M (Auxiliary DPDT Alarm Relay)
This relay option features a plug-in design and may be configured
for common alarm, zone alarm, or selective multiple alarm input
operation. Contacts are rated 10 amp @ 24 VDC or 115 VAC.
Option N (Auxiliary DPDT Trouble/Supervisory Relay)
Option N provides a plug-in relay that can be configured for
common trouble, zone trouble, or selective multiple trouble input
operation. This option may also be utilized for supervisory alarm
functions which are not required to initiate a system fire alarm
condition. Contacts are rated 10 amp @ 24 VDC or 115 VAC.
O
ptions P, Q & R (Heavy Duty Multi-Pole Relays)
The heavy duty relay options consist of rugged 600 volt relays
that can be used for any alarm, trouble or supervisory function
requiring high power handling capabilities. These relays have the
advantages of a direct drive design which prevents an overlap
c
ondition between N.O. and N.C. contacts, plus convertible
contact cartridges with swing-around terminals for N.O./N.C.
convertibility. Contact ratings for Option P (4 pole), Option Q
(6 pole) and Option R (8 pole) relays are NEMA A600 and
NEMA P600.
Option S (Time Delay Relay)
This option consists of a plug-in time delay relay which com-
bines a solid state digital timing circuit with an electromechani-
cal relay. The relays operating delay is manually adjustable from
.6 to 60 seconds, and is typically configured to provide timed
operating delays of system outputs such as solenoid activation.
The Option S Time Delay Relay contains two SPDT contacts
rated 10 amp resistive @ 120 VAC.
External Key Operated Control Switches Option T
Option T consists of four externally mounted key operated switch-
es. These switches are used to duplicate the main control functions
normally operated by the momentary switches mounted on the
MB-97 Series Main Board inside the system enclosure. External key
switches consist of System Reset, Alarm Silence, Trouble/Super-
visory Silence and Lamp Test. All external key switches are
NEMA-4 rated.
Battery Charging Meters Option U
Option U consists of a DC volt meter and DC amp meter which
provide a numerical indication of the systems battery condition.
The amp meter continuously displays battery charger current draw.
To display the charger voltage level, it is necessary to manually
depress the volt meter read switch. While in the normal standby
“Power On mode, the voltage reading reflects the battery set and
charger level in a charging state. Readings taken in a “Power Out
mode reflect the actual battery set voltage level. Option U is not
available when the UC1 Universal Power Input Option is ordered.
Auxiliary Power Supplies Options V & W
Option V consists of the APS-1 Power Supervisory Module with
bridge rectifier and step-down transformer. The power supply
provides 5 amps of additional full wave rectified power for heavy
duty relays, or other high power demand devices that may exceed
the 7 amp capacity of the systems main power supply.
Option W utilizes the APS-1 Power Supervisory Module and a
switching regulated power supply. This option provides 7 amps of
additional regulated power for detection zones, solenoid release
circuits, auxiliary audible circuits, or any other devices that require
regulated power.
Both units are completely supervised. Should the unit fail, a trouble
signal illuminates the on-board trouble LED and allows the battery
backup source to supply the panel with the necessary power.
System Enclosures
The 2600HD Series is provided in NEMA- 4 rated enclosures.
These enclosures are intended for use indoors or outdoors, and are
designed primarily to provide a degree of protection against wind-
blown dust and rain, splashing water, hose directed water, and
damage from external condensation.