Each enclosure consists of a back box and door, fabricated of heavy
gauge steel, and finished in a durable red enamel finish. The enclo-
s
ure door utilizes a gasketed window which permits viewing of all
appropriate visual indicators while still maintaining the enclosures
NEMA rating and FM Approval. To prevent the buildup of danger-
ous battery gases within the sealed enclosure, emergency standby
batteries must be mounted in a separately ordered battery cabinet.
E
nclosure Module Height Width Depth
M
odel Space Inches (cm) Inches (cm) Inches (cm)
EHD4230 20 42 (107) 30 (76) 8 (20)
EHD4236 28 42 (107) 36 (91) 8 (20)
EHD4836 35 48 (122) 36 (91) 8 (20)
EHD6036 45 60 (152) 36 (91) 8 (20)
Field Expansion
The zone capacity and optional features of the 2600HD Control
Panel can be expanded after installation by utilizing an E2600HD
System Extender Panel. In its basic form, the extender panel pro-
vides additional detection zones only. On large and more complex
systems, design flexibility enables an extender to be configured to
duplicate many of the same options contained in the main
2600HD Control Panel, thereby maintaining complete system
integration and expansion capabilities. Consult Factory for assis-
tance in determining specific configurations.
FireSystem 2600HD Specifications
AC Supply 120 VAC 50/60 Hz, 1.75 amp max. or 240 VAC
50/60 Hz., .85 amp max.
Battery Supply 24 VDC, 4.5 to 60 ampere hour, Sealed Lead
Acid (Gel Cell).
Primary System Power 24 Volts Full Wave Rectified, 175 VA.
typical. Greater VA rating as required by system options.
System Regulated Power 24 VDC for system controls.
Main Panel Common Alarm Contact Ratings 2 amp @ 30
VDC, resistive load, latching.
Main Panel Common Trouble Contact Rating 2 amp @ 30
VDC, resistive load, selectable latching or non-latching.
Environmental Operating Conditions:
Ambient temperature: 32°-120°F (0°-49°C)
Humidity: Maximum 95% non-condensing.
Notification Appliance Circuits:
24 volts full wave rectified with battery standby. Maximum cur-
rent is 2 amp per circuit, 3 amp maximum combined. Requires
polarized audible devices.
All specifications are subject to change without notice.
How To Order
Step 1. Select the model number of the basic system control unit
and note module space.
2600HD1 - System control unit with Protectowire Alarm
Point Location Meter. Requires 10.0 module spaces.
2600HD2 - System control unit without Protectowire Alarm
Point Location Meter. Requires 9.0 module spaces.
2600HD3 - System control unit with PCLC Touch Screen
Graphic Annunciator. (Includes Alarm Location Meter and
Automatic Zone Alarm Scanner.) Requires 12.0 module spaces.
Step 2. Specify system input and back-up power option.
Option Mod. Space Description
GC1
120 VAC Power Input with Gel Cell
Battery Back-up
GC2
240 VAC Power Input with Gel Cell
B
attery Back-up
UC1 4.0 Universal Primary and Back-up Power
I
nput. Uninterruptible Second Source
Back-up Power required
Step 3.
Select system option ordering code letter(s) and show
quantity. Note module space(s) required by each option in the
system enclosure.
Option
Mod. Space Description
A 2.0 Two (2) Zone Class A Detection
Module
AA 2.5 Two (2) Zone Class A Detection
Module w/ I/O Interface (2600HD3
Systems Only)
B 2.0 Four (4) Zone Class B Detection
Module
BB 2.5 Four (4) Zone Class B Detection
Module w/ I/O Interface (2600HD3
Systems Only)
C 2.0 TRI-Wire Two (2) Zone Class B
Detection Module
CC 2.5 TRI-Wire Two (2) Zone Class B
Detection Module w/ I/O Interface
(2600HD3 Systems Only)
D—8 Zone Alarm Location Meter Scanner
1
D2
16 Zone Alarm Location Meter Scanner
1
D3
32 Zone Alarm Location Meter Scanner
1
D4
48 Zone Alarm Location Meter Scanner
1
E 2.0 Four (4) Circuit Switch Supervisory
Module (Class B)
EE 2.5 Four (4) Circuit Class B Supervisory
Module w/ I/O Interface (2600HD3
Systems Only)
F 2.0 Two (2) Circuit Switch Supervisory
Module (Class A)
FF 2.5 Two (2) Circuit Class A Supervisory
Module w/ I/O Interface (2600HD3
Systems Only)
G (1st. Barrier) Intrinsic Safety Barriers, Class B
2
2.0 (Detection/Supervisory Circuits Only)
(Ea. Addl) TRI-Wire Zones Require (2) Barriers/
1.0 Zone)
H 1.0 Two (2) Circuit Solenoid Monitor &
Release Module, 24 VDC
HH 1.0 Two (2) Circuit Solenoid Monitor &
Release Module, 24 VDC Star Model D
Valve
1
This option not available on 2600HD2 or HD3 Systems.
2
This option is not available with system ground fault detection.