16
available from The Protectowire Company.
While it is not possible to stock a standard fas-
tener for every conceivable installation, alter-
native fasteners may be available on special
order. Please contact the factory for assistance
with your specific installation requirements.
Drilling Holes
Care in drilling holes through partitions and
beams is the first element of good installation.
Properly located holes work for the installer
by helping to hold the Detector in place.
Improperly located holes work against him by
requiring additional fastenings and increased
risk of mechanical damage to the Detector.
Installation Warnings
Protectowire is not fragile, but crushing or
pinching will injure it. The results of such
injury may not appear at once and may not
be obvious by the outward appearance of the
wire, but damage to the outer jacket or
unnecessary mechanical stress applied to the
wire during installation may cause “false
alarms” later on. Therefore:
DO NOT leave it on the floor and walk on
it or set ladders on it during installation.
DO NOT install it with commercial fasten-
ers unless specially approved by The
Protectowire Company.
DO NOT place it where it will be subject to
mechanical damage by equipment processes.
DO NOT overtighten the fasteners as this
may breach the outer jacket or crush the
inner insulation, causing unwanted alarms.
All fasteners must allow the wire to expand
and contract with temperature changes.
DO NOT over stretch the Protectowire runs,
some wiresag between fasteners is normal.
DO NOT MAKE 90° BENDS IN THE
DETECTOR.
DO NOT hold the wire with pliers to make
bends. All bends should be made with the
fingers and consist of rounded turns with
a minimum 2.5 inch (6.4 cm) radius.
DO NOT use wire nuts or other similar
devices. All connections must be made via
terminals and/or Protectowire approved
splicing devices.
DO NOT PAINT THIS DETECTOR, per UL
and FM requirements.
Figure 15
Figure 16
Figure 17
Figure 18