Przeglądanie stron 20
18
spaced as shown in Figure 20. When additional
cables are pulled into the tray they should also
be placed below the Detector.
Figure 20A illustrates the application of BC-2,
CC-2, CC-10, and HPC-2 mounting clips to
various types of cable trays.
Conveyors
Belt type (overhead installation) Figure 21
illustrates Protectowire Linear Heat Detector
with Type M messenger wire installed directly
over the conveyor to be protected. Whenever
possible, the Detector should be fastened to a
covering which is not more than 7.5 feet
(2.3m) above the conveyor belt and which is
in a horizontal plane or parallel to the line of
the conveyor. This will act as a heat collector
and will provide earlier detection. Support is
provided by messenger wire* which is fas-
tened with a turnbuckle at a maximum dis-
tance of 250 feet (75.7m). Approved interme-
diate fastening devices are used at intervals of
15 feet (4.5m) to 20 feet (6.0m) to ensure
detector tautness.
Figures 21A and 21B illustrates Protectowire
Linear Heat Detector with Type M messenger
wire installed on either side of the belt in the
area between the idler and the roller. Support
is provided by messenger wire* which is fas-
tened with a turnbuckle at a maximum dis-
tance of 250 feet (75.7m) to ensure Detector
tautness. Approved fastening devices are used
at each idler to avoid detector contact with
moving parts.
Belt side installation - See Figures 21C and
21D. (a) A third optional location for installa-
tion of Protectowire Linear Heat Detector is
beside and slightly above the belt.
(b) Install the Detector with Type M messen-
ger wire* on both sides of the belt beneath a
3 x 3 x 1/8 inch (7.6cm x 7.6cm x .3cm) angle
iron which is used as a heat collector and a
support. The angle iron should be located 3
to 4 inches (7.6cm to 10.2cm) above the belt
and directly over the line of the outboard
roller bearings.
(c) Support the Detector by securing the mes-
senger wire to turnbuckles and eyes located at
intervals of up to 250 feet (75.7m) and also by
the use of Protectowire approved fasteners
Figure 21C
Figure 21D
Belt type (idler arm installation)
Figure 21
Figure 21A
Figure 21B
Protectowire
Linear Heat
Detector
Protectowire Linear Heat Detector
End-of-line resistor/box