Protectowire 2000 FireSystem Instrukcja Użytkownika Strona 6

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 33
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 5
3
Copper feed wire, of an approved type, with a
minimum conductor size of 18 AWG, shall be
installed from the control panel out to the
hazard area where it is then connected to the
beginning of the Protectowire portion of the
circuit. To determine the recommended wire
gauge size and maximum length of copper
feed wire which may be used on each initiat-
ing circuit of a Protectowire FireSystem
Control Panel, refer to Table 1.
The Protectowire portion of every initiating
circuit shall terminate at each end in an
approved zone box, end-of-line zone box, or
other approved junction box provided as part
of the system. Strain relief connectors, Series
SR-502, shall be installed in all junction boxes
where Protectowire enters or exits the enclo-
sure, in order to hold the cable securely and
maintain dust and moisture tight conditions.
All zone box enclosures shall be rated and
approved for use in the environment where
they will be installed.
All electrical connections made within each
zone box between Protectowire and the cir-
cuitsinterconnecting copper wire or end of
line device, shall be made via terminals. The
Protectowire Company supplies zone boxes,
identified by the letters QC, which contain a
compression type terminal strip which allows
the installer to directly connect Protectowire
conductors to the terminals. In all other cases,
PFL Flexible Leads must be used to connect
Protectowire conductors to electrical termi-
nals. PFL’s consist of a twisted pair of soft cop-
per wires each with a PWS Splicing Sleeve
staked on one end, and insulated with slip-on
vinyl tubing. One lead is secured to each con-
ductor by bending as in making a PWS splice,
and insulated and taped in the same way (See
Figure 7A). The use of wire nuts or other sim-
ilar wiring devices not specifically approved
by The Protectowire Company, is not recom-
mended and shall be considered a misappli-
cation of the product.
Figures 1 and 1A depict the typical field wiring
of a ZB-4-QC-MP Zone Box in a Class B detec-
tion circuit of a fire alarm system using
Protectowire Linear Heat Detector. Figure 1B
depicts the field wiring utilized in a Class A
type detection circuit. It is important to note
that in each case, Protectowire may be con-
nected directly to the QC type terminals and
that all bends in the Detector should have a
radius of not less than 2.5 inches (6.4 cm).
GGeenneerraall PPrriinncciipplleess
Protectowire must be installed in continuous
runs without taps or branches to comply with
locations and spacing prescribed by the approv-
ing authorities. Except for zoning requirements
(alarm source indication) the length of each run
is limited, and controlled by the electrical char-
acteristics of the control equipment to which the
Detector is connected.
The Protectowire Company’s FireSystem
Control Panels have been specifically designed
for compatible operation with Protectowire
Linear Heat Detector. Each FireSystem Control
Panel has been approved for operating
Protectowire Linear Heat Detector, approved
smoke detectors or a combination of the two
devices on the same initiating circuit. The max-
imum quantity of detectors and length of sen-
sor cable will vary based upon the specific
control panel utilized. Please refer to the
Maximum Copper Feed Cable Length vs.
Wire Gauge (Diameter)
For Protectowire FireSystem Initiating Circuits
Initiating Circuits with Protectowire Alarm Point
Location Meter (18 ohms offset)
MAX. LENGTH OF
AWG* DIA. 2 CONDUCTOR CABLE
#18 1.02 mm 1,360 feet (414 m)
#16 1.27 mm 2,200 feet (670 m)
#14 1.63 mm 3,500 feet (1,067 m)
#12 2.05 mm 5,500 feet (1,676 m)
Initiating Circuits Without Alarm Point Location
Meter (Max. Resistance 100 ohms)
MAX. LENGTH OFF
AWG* DIA. 2 CONDUCTOR CABLE
#18 1.02 mm 7,600 feet (2,316 m)
#16 1.27 mm 12,200 feet (3,719 m)
#14 1.63 mm 19,400 feet (5,913 m)
#12 2.05 mm 30,800 feet (9,388 m)
*American Wire Gauge
Table 1
Przeglądanie stron 5
1 2 3 4 5 6 7 8 9 10 11 ... 32 33

Komentarze do niniejszej Instrukcji

Brak uwag