Self Storage Warehouses
In self-storage facilities, Protectowire may be
easily installed longitudinally in each building
thereby covering each individual storage com-
partment. To actually isolate the alarm loca-
tion, a Protectowire FireSystem Control Panel
with Alarm Point Location Meter may be used.
By referencing the linear distance of the alarm
point displayed on the meter to the footage
represented in each cubicle as noted on a
facility site plan (Figure 29) mounted next to
the control panel, the location of the alarm
condition can be easily identified.
The special applications which have been dis-
cussed in this section of the manual, represent
only a small number of the potential hazards
where Protectowire may be applied. This man-
ual is intended to provide general principles
only, therefore, the layout illustrations are “typ-
ical” in nature, and may require modification
or adjustment based upon an actual engineer-
ing evaluation of the specific hazard and it’s
relevant factors. If your specific application is
not shown here, or if you need additional
product application information or assistance,
please contact The Protectowire Company.
IInnssppeeccttiioonn aanndd TTeessttiinngg
This section covers the minimum recom-
mended requirements for inspection, and
testing Protectowire Linear Heat Detector. In
general, the requirements follow those rec-
ommended in NFPA 72 for fixed-temperature,
non-restorable line type heat detectors. This
manual does not cover inspection, testing or
maintenance of other related devices or com-
ponents of the fire alarm system.
Visual Inspection
Visual inspections of the installed system shall
be made to ensure that there have been no
changes to the installation site, building struc-
ture, or environmental factors that can effect
equipment performance. Visual inspections
shall be performed upon initial equipment
installation and at least semiannually thereafter.
A more frequent schedule may be used if
required by the authority having jurisdiction.
Because Protectowire is frequently used in spe-
cial applications where it may be inaccessible
for safety considerations such as continuous
process operations, or excessive height, it shall
be inspected during scheduled shutdowns
where approved by the authority having juris-
diction. In all cases, however, the extended
interval should not exceed 18 months.
Test Frequency
As an initiating device, testing Protectowire
Linear Heat Detector should be an integral
part of a complete inspection and test pro-
gram designed to ensure reliable operation
and service of the entire fire detection/sup-
pression system. Classified as a heat detector,
Protectowire shall be tested upon initial
installation and on an annual basis thereafter,
unless a more frequent schedule is required
by the local authority having jurisdiction.
Figure 29