spaced about 15 feet (4.5m) to 20 feet (6.0m)
apart to limit drooping and avoid contact with
moving parts.
(d) An alternate method is to use the Detector
without messenger wire and fasten the
Detector directly to the angle iron at intervals
of 5 feet (1.5m) to 10 feet (3.0m) with
approved mounting clips.
*The use of messenger wire is optional; how-
ever, when not employed additional fasteners
may be required.
Power Distribution Apparatus
Figure 22 illustrates Protectowire Linear Heat
Detector laced through a motor control panel.
It is secured with PM-3 wire straps to the appa-
ratus being protected. Other equipment that
may be protected in the same manner includes
transformers, switchgear, substations, resistor
banks, etc. where ambient temperatures do
not exceed the Detector’s rating.
Dust Collectors/Baghouses
Figure 23 illustrates Protectowire Linear Heat
Detector, supported by angle brackets,
installed 30 inches (.8m) above the inside
base of a dust collector.
From the base junction box the Detector is
circled around the interior of the outer siding
then run in conduit to the center tube where
the Detector is circled as shown. The Detector
is then run in conduit to the top of the col-
lector where it is supported on messenger
wire in the pattern shown in Figure 23A.
The Detector may also be installed around the
blower motor frames for early detection of an
overheating condition.
Figure 23A
Figure 23
Figure 22
Protectowire
Linear Heat Detector
on messenger wire
Top view horizontal section